- Voltage: 176—275VAC Over-voltage tested to 325Vac
- Frequency: 47-63Hz
- Peak Inrush Current: <50A
- Power Factor: 0.99 typical
- Efficiency: ~93% with 230VAC source,
50 to 100% load
- Hold-Up Time: 10mS min.
- Input Overcurrent: (internal) 25 A Fuse
|
|
- Primary Voltage -48V, -54.5V. Custom outputs available, consult Factory
- Power: 4,300W, -20 to +55°C, 176-275Vac
3,500W, -20 to +75°C, 176-275Vac
1,900W, -20 to +55°C, 90-275Vac
810W, -20 to +75°C, 90-275Vac
- Auxiliary output: 12V/ 0.1A
- Accuracy: ± 50mV
- Ripple & Noise: 1% V P-P Measured with 20Mhz Bandwidth
- Line Regulation: Less than ±0.25%
- Load Regulation: ±1.0% from no load to full load (droop load share)
- Parallel Use: May be paralleled with other like units for increased system output, redundant diode included
- Current Sharing: Slope program current share, (droop)
- Temperature Coefficient: < ±0.02% per°C
Acoustic Noise < 67dBA at nominal input and full load
|
| |
|
| |
|
| |
| |
|
| |
|